Customization: | Available |
---|---|
Clapboard: | without Clapboard |
Filter Number: | 0 |
Still deciding? Get samples of US$ 9.9/A4
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
It is mainly used for primary filtration in ventilation equipment, dust removal equipment and air supply systems in various high temperature and fireproof environments.
Main components |
Special flame retardant synthetic fibers |
Humidity resistance (relative humidity) | ≤100% |
Filtration class |
G2,G3,G4(EN779) |
Smoke density Oxygen index | ≤200(TB/3237) |
Filter object |
≥5μm Coarse dust and foreign matter |
Oxygen index | ≥32(TB/3237) |
Final resistance |
250Pa(suggestion) |
Flame retardant grade(import) | Class3(JACA No.11A-2003) |
Average weighting efficiency |
90%(ASHRAE52.1-1992) |
Model |
Standard Size |
Gram Weight |
Weight (g/m²) |
Dust holdingCapacity (g/m3) |
Rated air velocity (m/s) |
CMH |
Temperature resistance ºC |
I.N.P (Pa) |
F.N.P (Pa) |
RT-HT180 |
1.6m*20m |
10mm |
250 |
450 |
1 |
3600 |
<180 |
25 |
250 |
RT-HT240 |
500mm*500mm |
20mm |
450 |
600 |
1 |
3600 |
<240 |
45 |
250 |
800mm*800mm |
20mm |
450 |
600 |
1 |
3600 |
<240 |
45 |
250 |
|